Fueling Products

Submersible Pumping Systems

  • More Information

  • Download Reference

Other Solutions

Slideshow image

1-1/2 hp Fixed Speed Submersible Turbine Pumps

FE Petro has contributed innovative product designs for submersible pumps throughout the 1990’s, and into the 21st Century. With the introduction of a 2hp fixed speed submersible, FE Petro also introduced the MagShell™ innovation to improve the profitability of your retail operations.

Specifications

Power Requirements

  • 1-1/2 hp Fixed Speed models require single phase, 208-230 VAC, 60 Hertz incoming power
  • 1-1/2 hp Fixed Speed models incorporate a starting & running capacitor, with internal bleed resistor, rated 370 Volt, 15 microfarad
  • STP-SCI Single Phase Smart Controllers and STP-CBS Single Phase Control Boxes are available for 1 1/2 hp pump control
  • Max Motor Draw: 11 amps

Pump Motor

  • 1-1/2 hp Fixed Speed, 3450 rpm, multi-stage centrifugal type pump motor with integral, automatic, thermal overload protection
  • Available in Standard Pressure (2 stage) model, Max Flow = 100 gpm, Max Pressure = 34 psi
  • Available in High Pressure (H150, 3 stage) model, Max Flow = 65 gpm, Max Pressure = 46 psi

Liquid Compatibility

  • Max liquid viscosity: 70 SSU @ 60°F (15°C)
  • Standard STP (Non-AG) models are UL and cUL listed for fuel mixtures containing up to 15% Ethanol or Methanol, and 20% MTBE, 20% ETBE, or 17% TAME with gasoline.
  • STPAG (Alcohol-Gasoline) models are UL and cUL listed for fuel mixtures containing up to 100% Ethanol or Methanol, and 20% MTBE, 20% ETBE, or 17% TAME with gasoline.
  • 1-1/2hp Fixed Speed models can also be used with Diesel Fuels, Fuel Oils, Kerosene, Avgas, and Jet Fuels in a non-gelled pourable state.
  • All wetted elastomers are made of a high grade, fluorocarbon viton compound.

Standard Features

  • 1-1/2 hp Fixed Speed models are available in Variable Length and Fixed Length options
  • Check Valve: 2 3/4 diameter fluorocarbon viton seal constructed on cast aluminum body and steel backing washer
  • Pressure Relief Valve: available in four pressure relief settings, integral to Check Valve. Standard Model relieves at 40 psi and resets above 35 psi.
  • Syphon: venturi type syphon primer supplied with every submersible. Syphon Check Valve and Secondary Syphon sold separately.
  • Air Eliminator: every submersible includes tank return path, with one-way check valve, to provide active air elimination
  • Electrical Disconnect: electrical yoke for positive contractor disconnect during service

Approvals

  • 1 1/2 hp Fixed Speed models are UL and cUL listed
  • Consult factory for other applicable approvals

Quality Certification

  • Franklin Fueling Systems is an ISO 9001 Certified Manufacturer

Designation System


Click here to view the diagram.

    A typical turbine model designation has up to five
    components to define the pump being supplied as follows:
    STP YYYYY A - B - C
    STP = Basic Model Designation

    YYYYY = Factory Installed Options

    Model designations may include one or more of the
    following characters in alphabetical order:
    AG = alcohol-gasoline Compatible
    (100% ethanol or methanol capable) Note: Standard
    models 0% to 15% ethanol or methanol capable
    F = Floating suction adapter (1 1/2” NPT Female adapter)
    H = High pressure (45 psi deadhead output)
    K = Intake filter screen (IFS, factory installed to PMA)
    *R = Model R check Valve
    (24 psi relief / 22 psi reset for PLLD)
    *W = Model W check Valve
    (16 psi relief / 13 psi reset for PPM4000)

    *Note: If not otherwise specified, all STP models supplied with
    standard model check valve (40 psi relief / 35 psi reset for MLD &
    LS300)

    A = Pump Motor Horsepower Rating
    150 = 1 1/2 hp fixed speed

    B = Model Length**
    VL1 = variable length range #1
    VL2 = variable length range #2
    VL3 = variable length range #3

    **Note: VL2 models fit 94% of all known installations. See 1 1/2 hp
    fixed speed model Number tables for specific model length range
    details.

    C = Riser Pipe Length

    Note: Riser pipe length is expressed as two numeric characters
    that indicate the total length of the riser in inches. Riser pipes are
    available from 7” to 69” in one inch increments (add’l charge for
    risers 31” or longer)

Ordering Information

1-1/2 hp Fixed Speed, Variable Length Submersible Turbines Pumps

Non-AG Model Number Description Model*Length Range
STP 150 - VL1 1 1/2 hp Fixed Speed 60”-88”
STP 150 - VL2 1 1/2 hp Fixed Speed 91”-152”
STP 150 - VL3 1 1/2 hp Fixed Speed 123”-214”
STP H 150 - VL1 High Pressure, 1 1/2 hp Fixed Speed 61”-89”
STP H 150 - VL2 High Pressure, 1 1/2 hp Fixed Speed 92”-152”
STP H 150 - VL3 High Pressure, 1 1/2 hp Fixed Speed 124”-215”

 

Alcohol-Gasoline Model Number Description Model* Length Range
STPAG 150 - VL1 AG, 1 1/2 hp Fixed Speed 60”-88”
STPAG 150 - VL2 AG, 1 1/2 hp Fixed Speed 91”-152”
STPAG 150 - VL3 AG, 1 1/2 hp Fixed Speed 123”-214”
STPAG H 150 - VL1 AG, High Pressure, 1 1/2 hp Fixed Speed 61”-89”
STPAG H 150 - VL2 AG, High Pressure, 1 1/2 hp Fixed Speed 92”-152”
STPAG H 150 - VL3 AG, High Pressure, 1 1/2 hp Fixed Speed 124”-215”

 

    1. Above models are UL and cUL listed for compatibility with fuel mixtures containing:
    STP (Non-AG) = up to 15% Ethanol or Methanol with Gasoline, and 20% MTBE, 20% ETBE, or 17% TAME with Gasoline.
    STPAG (Alcohol-Gasoline) = up to 100% Ethanol or Methanol with Gasoline, and 20% MTBE, 20% ETBE,
    or 17% TAME with Gasoline.
    2. All models are supplied with Standard Check Valve unless factory option “R” or “W” is specified.
    3. All above models require Single Phase, 208-230 VAC, 60 Hertz incoming power
    * Model Length (B) defined as the dimension from Turbine Manifold bottom to Pump Motor inlet.
    ** 4” Riser Pipe, if supplied locally, must be 4 1/2” OD by 3/16” wall thickness tubing.
    *** For Riser Pipe lengths 31” to 69”, adder charge applies.


Factory Installed Options (specified in Model Number at time of STP order)

Model Designation Description
F Floating Suction Adapter (1 1/2” NPT Female) must be factory installed
K IFS (Intake Filter Screen) factory assemblied to Pump Motor Assembly
R Model R Check Valve factory installed (for Veeder Root PLLD Line Leak)
W Model W Check Valve factory installed (for Red Jacket PPM4000 Line Leak)

Field Installed Options (1-1/2 hp Fixed Speed specific accessories)

Part Number Description
5800100215
Single Phase Smart Controller (when purchased without a 4 inch STP)
5800100215
Single Phase Smart Controller (when purchased with a 4 inch STP)*
5800300100
STP-SCI (Dispenser Hook Isolation for 110V dispenser handle switches, up to 8 each)
402312921
STP-DHI-SCI (combo Dispenser Hook Isolation with factory wired STP-SCI)*
402313921
STP-DHI-CBS (combo Dispenser Hook Isolation with factory wired STP-CBS)
400818921
STP-CBS (Single Phase Control Box with lockout switch, 110V coil)
400137908
Syphon Check Valve (Alcohol-Gasoline compatible) when ordered with STP
402507930
Secondary Syphon Kit (when two syphon primes are required for one STP)
402459931
Model 65 PSI Check Valve (for Slave of manifolded STP’s with Veeder Root PLLD)
    *When purchasing STP-SCI or STP-DHI-SCI in equal quantities of Fixed Speed 4 inch STPs, the STP-SCI or STPDHI-
    SCI will be invoiced at special discount pricing.