Line Leak Detection System

Line Leak Detection System

The TS-LS300 line leak detection system provides standalone leak detection for up to four lines. It can run independently or with any TS-1001, TS-2001 or TS-508 tank gauge.

LS300 Highlight.psd

STANDALONE LINE LEAK DETECTION

The LS300 line leak detection system uses AUTO-LEARN® technology to  automatically learn the pressure characteristics of each pipeline for precision leak detection.


  • No pipe type and length programming required.

  • Monitors flexible, steel and/or fiberglass pipelines in any combination up to certified maximum values.

  • Works with submersible pumps generating 25 psi or more.

  • Automatically performs 3.0 gph, 0.2 gph and 0.1 gph line tests.

  • Positive submersible pump shutdown in the event of a leak.

  • Can be monitored through ATG and System Sentinel™.

  • Third party certified for 0% probability of false alarm.

  • Eliminates the need for factory calibration or on-site field judgments for set-up.

  • For use in rigid, flex and rigid/flex piping configuration.

  • Immediate notification of alarm condition.

  • Provides printed compliance reports.

Console Specifications

  • Number of lines monitored: 1, 2, 3 or 4.
  • Dimensions: 11" × 12" × 4".
  • Power requirements:
  • 115 VAC - +15%, -10%, 100 Watts maximum, 1 Amp maximum.
  • 230 VAC - +15%, -10%, 100 Watts maximum, 0.5 Amp maximum.
  • Operating temperature: 20° to 122 °F (10° to 50 °C).

Leak Sensing Transducer Specifications

  • Number of lines monitored: 1.
  • Dimensions: 6-1/4" × 2" NPT.
  • Applicable liquids: motor fuels.
  • Power requirements:
    • 10 to 20 VDC from console.
  • Operating temperature: -40° to 149 °F (-40° to 66 °C).
  • Operating pressure: 0 to 100 psi (0 to 689 kPa).
  • Belden™ cable: #9363-22 AWG, #9364-20 AWG or #9365-18 AWG.
  • Max. sensor to console cable distance:
    • 500' (152.4 M).
  • Sensor port fitting: 2" female NPT.
  • Sensor material: anodized aluminum body and stainless steel sensor.
  • Intrinsic safety rating: Class 1, Div. 1, Group D, II (1) G [EEX la] IIA T4

Capabilities

  • The TS-LS300 performs a 3.0 gph leak and pressure test after every dispense. Upon detection of a failed test, the LS300 will alarm and positively shutdown the affected turbine.
  • The TS-LS300 continuously monitors pressurized lines for thermally stable conditions and performs a 0.2 gph monthly and 0.1 gph annual precision leak test during the thermally stable union.
  • AutoLearn™ line leak detection technology is also available with the TS-LS500, part of the EVO™ Series 550 and EVO™ Series 5000 fuel management systems.

Approvals/Certifications

  • UL
  • Third party certification of leak detection capabilities

TS-LS300, 115 VAC 50/60 Hz Models

Intrinsically Safe

For new installations where separate low voltage conduits can be used.

Model Number Description
TS-LS300/2 2-line console with line calibration kit
TS-LS300/3 3-line console with line calibration kit
TS-LS300/4 4-line console with line calibration kit
  • All AutoLearn™ models include the TPI turbine pump interface module.

TS-LS300, 230 VAC 50/60 Hz Models

Intrinsically Safe

For new installations where separate low voltage conduits can be used.

Model Number Description
VS-LS300/2 2-line console with line calibration kit
VS-LS300/3 3-line console with line calibration kit
VS-LS300/4 4-line console with line calibration kit
  • All AutoLearn™ models include the TPI turbine pump interface module.

Interface Cable

For connecting two AutoLearn™ consoles together.

Model Number Description
TSSP-ALICBL AutoLearn™ interface cable

Alternative Fuels Accessories

Model Number Description
TS-AFALNIP Leak generator needle valve kit required for E85 installations

Manuals