Automatic Tank Gauges

EVO™ 200 & EVO™ 400

EVO 400 Front Splash.psd
EVO 400 Front Splash.psd EVO 400 Front Splash.psd
Automatic Tank Gauges

EVO™ 200 & EVO™ 400

EVO™ 200 & EVO™ 400 provide highly accurate inventory management and containment monitoring for small to mid-size fuel systems. With pre-configured hardware and customizable software options, the EVO™ 200 & EVO™ 400 provide straightforward tank level monitoring and compliance.

Their simple setup and operation, remote connectivity, and advanced security features protect your fuel system while keeping you directly connected to vital site data whenever, and wherever. The highly-intuitive, full-color, icon-based touch screen provides user-friendly on-site access to inventory, alarm, and compliance data.

EVO 200 EVO 400 Highlight Hero.psd

NEVER STOP EVOLVING

We are driven by our pursuit to innovate, simplify, secure, and connect every station owner to their fuel management system. EVO™ 200 and EVO™ 400 ATGs feature simple setup and operation, remote connectivity, and advanced security features to protect your fuel system while keeping you directly connected to vital site data whenever, and wherever.


Highly Capable

EVO™ 200 and EVO™ 400 allow you to make informed, data-driven inventory management decisions with features like, inventory monitoring, tank testing, and containment compliance monitoring.

Simple Interface

A full-color 7” LCD touchscreen serves up one of the most intuitive user interfaces available with simplified user features you won’t find anywhere else.

Secure Data

EVO™ Series ATGs keep your site in compliance and protected from security threats with customizable user roles, user activity tracking, and up to 3-years of data back-up to protect against power outages or other system interruptions.

TECHNICAL ADVANTAGES

EVO-Highlights-Input-Capacity.png

Input Capacity

EVO™ 200 can support any combination of up to 6 sensors and probes, while the EVO™ 400 can support any combination of up to 14 sensors and probes.

EVO-Highlights-Turbine-Pump-Interface.png

Turbine Pump Interface

Enhanced remote pump monitoring and control including pump-in-water automation, clogged intake escalation, tank leveling, and tank priority.

EVO-Highlights-Remote-Communication.png

Remote Communication

The FFS PRO™ Connect web interface allows users to securely connect directly to an EVO™ Series ATG from any web enabled device.

EVO-Highlights-Inventory-Reconciliation.png

Inventory Reconciliation

Inventory Reconciliation is an automated leak detection function that analyzes tank volume, deliveries, and sales data to detect fuel loss or gains with a high level of accuracy.

EVO-Highlights-Tank-Autocalibration.png

Tank Autocalibration

Eliminate discrepancies in delivery reporting and daily reconciliations caused by inaccurate tank information programmed into the ATG with this function that automatically generates a highly accurate tank strapping chart.

EVO600-Illustrations-flowratemonitoring.psd

NEW: Flow Rate Monitoring

Detect and react to potential slow flow issues with automated daily reporting and alarms, helping to improve flow rates and dispenser throughput.

EVO Series Group Wide.psd
SIMPLICITY & VISIBILITY

A full-color 7” LCD touchscreen serves up one of the most intuitive user interfaces available with simplified user features you won’t find anywhere else. You choose your home screen, you program your product colors, and you choose what shows up on your Favorites screen. Customize the interface to meet your business needs the way you operate. Check out the interactive demo below. Note: Certain features are only available on the EVO™ 600/6000.

CLICK ON THE INTERACTIVE TOUCHSCREEN BELOW

 

EVO200 EVO400 Icon Based.psd

Icon-Based Design

Designed to be understood easily and operated intuitively. It’s simple to operate for new users and can reduce the amount of training required to operate.

EVO200 EVO400 One Touch.psd

One Touch Buttons

You can customize these home screen buttons to automate and carry out anything from complex, multi-function processes to simple daily delivery report generation - all with the touch of a single button.

EVO200 EVO400 Quick Jump.psd

Quick Jump Menu

Navigate quickly from application to application with ease. This time-saving menu makes the interface’s structure extremely shallow, simple to navigate, and reduces the amount of steps it takes to accomplish tasks.

EVO200 EVO400 Security Wide.psd
SYSTEM SECURITY

EVO™ Series ATGs help keep sites in compliance while providing marketers with the highest level protection from the security threats facing our industry.

User Roles

Customizable user roles and log-in security protect against unwanted access and track user activity.

Data Back-Up

Stores up to 3-years of data to provide back up security from power outages or other system interruptions.

Secure WiFi

Optional WiFi allows secure and protected onsite viewing of inventory levels for fuel delivery drivers.

EVO200 EVO400 Remote Wide.psd
REMOTE CONNECTIVITY

The FFS PRO® Connect web interface allows you to securely connect directly to your EVO™ Series ATG from any web enabled device. It automatically scales for tablets and smart phones, meaning no app to download.

INTERACTIVE DEMO
EVO 200 EVO 400 Connect Highlight.psd

FFS PRO® CONNECT

FFS PRO® Connect displays real-time data allowing precise delivery scheduling and efficient site management.  It also provide immediate notification of alarms so quick corrective actions can be taken.

Centralized Control

Provides centralized control of all compliance information - such as tank testing data and leak detection sensor status.

Reporting

A wide variety of reports can be custom-scheduled, displayed, printed, or emailed at specific times.

Simplified Setup

Simplifies setup and programming with the ability to download specific sections or the entire configuration from one ATG to another.

EVO200 EVO400 TPI Wide.psd
TURBINE PUMP INTERFACE

Turbine Pump Interface is a powerful tool that creates a network between your Submersible Turbine Pump (STP) controllers and EVO™ Series ATGs. Through TPI, the tank gauge can be programmed to respond to faults in the submersible pumping system and react with intelligence that pump controllers alone cannot.

SEE TPI IN ACTION

Pump In Water Automation

When the water level in a tank approaches the pump intake, the tank gauge will enter alarm mode and automatically shut down the pump, protecting the system and consumers from water being pumped from that tank.

Leveling & Priority Modes

When managing two storage tanks of the same product ‘Leveling Mode’ can keep both tanks at the same percentage full without the use of a syphon bar between the two tanks.

Remote Pump Interaction

By networking the intelligent controllers to the fuel management system via TPI, a technician can remotely connect to the site to review the logged event history and view the status.

EVO 600 Flow Rate Wide.psd
FLOW RATE MONITORING

Improve dispenser throughput and maintain fast flow rates with the ability to detect and react to potential slow flow issues before they impact business with Flow Rate Monitoring. Available as a software option on new EVO™ Series ATGs or as a field upgrade option, Flow Rate Monitoring delivers ongoing flow rate performance data, flow rates for each fueling point, and provides a notification if transactions dip below a user-defined set point.

FLOW RATE MONITORING SELECTION GUIDE

Know Your Flow

Monitor for and ensure fast and consistent dispenser throughput with daily reports and alarm notifications regarding flow rate performance.

Performance Monitoring

Sales and dispensing duration data are automatically reconciled to help you better understand the flow performance of every fueling point.

Proactive Maintenance

Often, slow flow rates can indicate that a dispenser filter needs to be changed. Be proactive in calling for maintenance, getting dispensers back to peak performance sooner.

EVO Select Wide.psd
FIND THE RIGHT EVO™ SERIES ATG FOR YOUR SITE

The EVO™ Series family of ATGs offers four different options with right-sized features to meet the requirements of your specific application, size, and compliance needs. Which ATG is right for your application?

ATG SELECTION GUIDE

With pre-configured hardware and customizable software options, these ATGs provide straightforward tank level monitoring and compliance. Their simple setup and operation, remote connectivity, and advanced security features protect your fuel system while keeping you directly connected to vital site data whenever, and wherever.

  • Included Features: Inventory monitoring, Turbine Pump Interface (TPI) capability for enhanced and automated submersible turbine pump control, static tank testing, and containment compliance monitoring.

  • Optional Features: 24-hour Statistical Continuous Automatic Leak Detection (SCALD®), tank autocalibration, inventory reconciliation, and flow rate monitoring.

  • Both the EVO™ 200 & EVO™ 400 feature the capability to interface with probes and sensors in any combination up to 6 (EVO™ 200) or 14 (EVO™ 400).

  • Customizable user roles and log-in security features protect against unwanted access while keeping track of user activity
    within your system.
  • Streamlined setup and programming includes hardware auto-detection and wiring confirmation, multipoint tank charting, network printer auto-detection, and the ability to download and upload entire programming profiles from one to another.

  • Intuitive full-color 7" (17.78 cm) LCD touch screen interface provides simplified on-site access features including: 
    • Up to Six (6) One Touch Buttons that are custom programmed to carry out common automated tasks with a single tap.
    • A Quick Jump Menu that allows you to quickly maneuver from application to application using a single button.
    • Programmable product colors for each tank.
  • FFS PRO® Connect allows you to remotely connect to your EVO™ from any web-enabled device.

  • Optional WiFi allows secure and protected on-site viewing of inventory levels for fuel delivery drivers.

  • Supports MQTT protocol, the standard for IoT messaging, for enhanced security of data transmission.

Components

EVO200 Dims Comps.psd
  1. Cover
  2. LCD touch screen
  3. LED indicators
  4. Anunciator (audible alarm)
  5. RS-485
  6. Mini USB port
  7. Ethernet / USB port
  8. RS-232
  9. Knockouts
  10. Mounting holes
  11. Flip up panel (touch screen)
  12. Termination blocks
  13. Main board

General

Maximum tanks monitored 6 (EVO™ 200)/14 (EVO™ 400)
Maximum sensor input capacity  6 (EVO™ 200)/14 (EVO™ 400)
Lines capacity  6 (EVO™ 200)/14 (EVO™ 400)
Dry contact input channels 2
Relay output channels 2
Connectivity  Ethernet, RS-232, RS-485, standard USB, Mini-B USB, and WiFi (optional)
Display type  7" (17.78 cm) color LCD touch screen
Printer type External (network or USB)
Alarm  Internal audible alarm
LEDs  Alarm, warning, and power
Tank chart correction points  7,500
Applicable liquids  Petroleum, chemicals, and waste
Level units Inches, centimeters, and millimeters
Volume units  Gallons or liters (mass with density option)
Power requirements  110 to 240 VAC, 50/60 Hz, 2.6 Amps
Operating temperature 32° to 104° F (0° to 40° C)
Humidity  0-95% non-condensing
Dimensions  H: 8" (205 mm), W:13 ¾" (350 mm),D: 3¼" (83 mm)
Alarm set points  High/low product, water, and temperature
Technical Advantages  Inventory reconciliation/tank autocalibration/flow rate monitoring (optional)
Measurements  Density, mass, and phase separation measurement
Notifications  Email and SMS
Programming  Conditions
Monitoring  Back-up generator
Support  MODBUS™
Approvals  UL, cUL, ATEX, IECEx, GSA IT Security
Certifications
  • Third party certification of leak detection capabilities
  • Third party verified “MATURE” security posture level

 

Ordering Guide

ATG model, software and hardware options can be listed separately or combined when ordering. Systems shipped from the factory will list the combined part number. Complete part numbers have a specific order and are created using the following guidelines:

EVOX DW - TRFC

  • EVOX = Base Model Options
    • EVO200 = EVO™ 200 base model, up to 6 channels
    • EVO400 = EVO™ 400 base model, up to 14 channels
  • DW = Hardware Options (choose all that apply)
    • D = Display (color LCD touch screen)
    • W = WiFi
  • TR = Software Options (choose all that apply)
    • T = SCALD 24-hour tank testing
    • R or F
      • R = Reconciliation/Autocalibration
      • F = Reconcilliation/Autocalibration with flow rate monitoring
    • C = Enhanced logic conditions including value, counter, value compare, and latch

Example: EVO400DW-TR = EVO™ 400 base model, up to 14 channels with display, with Wifi, with SCALD, and with Reconciliation/Autocalibration.

EVO™ 200 & EVO™ 400 Hardware & Software Field Upgrades

The following software and hardware options can be added to customize your EVO™ once it's been installed in the field.

Internal Software Field Upgrades

Model Number Description
TS-TT (T) Statistical Continuous Automatic Leak Detection, 24 hour continuous tank testing software
TS-TRAC (R) Tank inventory reconciliation and autocalibration
TS-TRAC-F (F) Reconciliation/autocalibration and flow rate monitoring software
TS-FLOW Flow rate monitoring
TS-CON (C) Enhanced logic conditions including value, counter, value compare, and latch

Hardware Field Upgrades

Model Number Description
FMP-LCD (D) Display (color LCD touch screen)
FMP-WIFI WiFi upgrade for an existing EVO™ 200, EVO™ 400, EVO™ 600, or EVO™ 6000, includes 4.5" antenna
FMP-ETP External thermal printer, includes USB cable, power cord, one roll of thermal printer paper, and wall mount hardware
  • Note: The external printer measures 5.6" w x 5.2" h x 8.0" d (142 mm x 132 mm x 204 mm) and can be mounted to wall next to the EVO™ using the included hardware.

External Printer

Model Number Description
FMP-EPPC Case of 25 thermal printer paper rolls
FMP-ETP External thermal printer, includes USB cable, power cord, one roll of thermal printer paper, and wall mount hardware
  • The external printer measures 142mm X 132mm X 204mm (w x h x d) and can be mounted to wall next to the EVO™ Series ATG using the included hardware).

EVO™ 200 and EVO™ 400 Replacement Parts

Model Number Description
FMSP-24MB EVO™ 200 and EVO™ 400 replacement main board
FMSP-SOM Unregistered, replacement SOM (no WIFI)
FMSP-SOM-R Registered replacement SOM (no WIFI)
FMSP-UDP200 EVO™ 200 replacement input PCB
FMSP-UDP400 EVO™ 400 replacement input PCB
FMSP-LCD EVO™ 200 and EVO™ 400 LCD replacement
FMP-24FUSE EVO™ 200 and EVO™ 400 replacement fuse kit
FMP-24TRMBLK EVO™ 200 and EVO™ 400 replacement terminal blocks
FMSP-24CVR EVO™ 200 and EVO™ 400 without LCD replacement cover
FMSP-24CVRWD EVO™ 200 and EVO™ 400 with LCD replacement cover
FMP-EPPC Case of 25 thermal printer paper rolls
FMP-ETP External thermal printer, includes USB cable, power cord, one roll of thermal printer paper, and wall mount hardware
  • The serial number of the old SOM must be provided when ordering the FMSP-SOM-R or the FMSP-SOMW-R.

Manuals

Title Type Size
TB0721-02 Upgrading EVO2004006006000 Firmware.pdf PDF 0.59 MB
TB0123-02 Upgrading EVO 200_400_600_6000 Software Registration.pdf PDF 0.85 MB
TB0323-02 Connect External Printer to EVO Series Console.pdf PDF 0.24 MB
TB0218-04 EVO 200 & EVO 400 Sensor Selection Guide.pdf PDF 0.39 MB
228180003 EVO 200 and EVO 400 Automatic Tank Gauge Installation Guide.pdf PDF 2.47 MB
228180003CS EVO 200 and EVO 400 Automatic Tank Gauge Installation Guide.pdf PDF 2.77 MB
228180003FR r2 EVO 200 and EVO 400 Automatic Tank Gauge Installation Guide.pdf PDF 2.49 MB
228180015 r1 EVO 200 and EVO 400 Automatic Tank Gauges Programming Guide.pdf PDF 1.59 MB
228180015FR r1 EVO 200 and EVO 400 Automatic Tank Gauges Programming Guide.pdf PDF 1.78 MB
228180016 r1 EVO 200 and EVO 400 Automatic Tank Gauges Operation Guide.pdf PDF 3.2 MB
228180016FR r1 EVO 200 and EVO 400 Automatic Tank Gauges Operation Guide.pdf PDF 3.29 MB
228180016PL EVO 200 EVO 400 ATG Operation Guide.PDF PDF 3.29 MB
228180027 EVO 200 and EVO 400 LCD Display Installation Guide.pdf PDF 2.86 MB
228180037 EVO 200 and EVO 400 Cover Replacement Guide.pdf PDF 0.98 MB
228180038 EVO 200 and EVO 400 Fuse Replacement Guide.pdf PDF 2.23 MB
228180039 EVO 200 and EVO 400 Input Board Replacement Guide.pdf PDF 3.8 MB
228180040 EVO 200 and EVO 400 Main Board Replacement Guide.pdf PDF 5.05 MB
228180041 EVO 200 and EVO 400 SOM Card Replacement Guide.pdf PDF 3.39 MB
228180045 EVO 200 and EVO 400 FMP-ETP Installation Guide.pdf PDF 1.27 MB
228180045CS EVO 200 400 FMP-ETP Printer Installation Guide.pdf PDF 1.37 MB
000-1747 EVO 200 and EVO 400 Bid Specification.pdf PDF 0.97 MB
10000007526 EVO Postive Shutdown Reference Guide.pdf PDF 2.55 MB
10000014305 EVO 200_400 Read This First.pdf PDF 0.07 MB
AG-021 TS-CON Control Conditions Software Application Guide.pdf PDF 2.5 MB
10000011156 MODBUS Interface Programming Guide.pdf PDF 0.62 MB
10000014113 EVO Series Console Install Checklist PDF 0.09 MB

Drawings

Title Type Size
CD_FMS_TS-EXPC_001.pdf PDF 0.09 MB
CD_FMS_TS-EXPC_001.dwg DWG 0.48 MB
CD_FMS_EVO600_001.pdf PDF 0.1 MB
CD_FMS_EVO600_001.dwg DWG 0.38 MB
CD_FMS_EVO 400_001.pdf PDF 0.38 MB
CD_FMS_EVO 400_001.dwg DWG 1.25 MB
CD_FMS_EVO200-3D_001.stp STP 14.16 MB
CD_FMS_EVO200-3D_001.pdf PDF 0.55 MB
CD_FMS_EVO400-3D_001.stp STP 8.99 MB
CD_FMS_EVO400-3D_001.pdf PDF 0.55 MB

Assets